For selecting the proper size of a DanTaet protection system:
Read notes on dimensioning district heating systems
Employ nomogram below for dimensioning district heating systems
Protection systems for commerce and industry providing continuous leakage monitoring
in direct district heating installations.
Example
A district heating installation requires a water flow rate of 4 m³/h.
The acceptable pressure drop in the protection system is 10 kPa.
The nomogram shows that a DanTaet system with an equivalent
Kvs of 12 or more should be used, e.g., KMP-F10-M2.