Design Nomogram

For selecting the proper size of a DanTaet protection system:

  • Read notes on dimensioning district heating systems
  • Employ nomogram below for dimensioning district heating systems

spacer

Protection systems for commerce and industry providing continuous leakage monitoring in direct district heating installations.
System layout nomogram
spacer

Example

A district heating installation requires a water flow rate of 4 m³/h.
The acceptable pressure drop in the protection system is 10 kPa.
The nomogram shows that a DanTaet system with an equivalent
Kvs of 12 or more should be used, e.g., KMP-F10-M2.

spacer

Download nomogram in pdf-format (20kb)