Monitoring Functions
Volume Leak:
Volume leak alarm is given if the volume flow difference exceeds the set threshold
for two consecutive measuring periods each max. 210 seconds.
ALOHA®:
The patented ALOHA® mechanism enables the passage
of air pockets through the flow meters without causing false alarms, and
without altering the basic sensitivity of the system.
Thus system KMP-F offers optimum reliability.
Seepage: (OptiTight®)
The patented OptiTight® mechanism employs
individual control of the cut-off valves to test the installation tightness one or more
times daily, whereby even minute seepage may be detected.
System Error:
When a valve is closed - by tightness test or alarm - the system
checks its tightness. If a component fails, a System Error Alarm ensues.
Failure of any internal voltage supply causes a System Error Alarm. Functional failure
reported by Kamstrup MULTICAL® causes a System Error Alarm.
No cut-off results from System Error Alarm.
Alarm Functions
On leak errors, KMP-F will cut off the installation, issue visble and audible alarms,
and activate the alarm relay.
System error is reported via the alarm relay, and visibly and audibly when possible.
Valve error is reported visibly.
Leakage Alarm from KMP-F may be read out via any communication module in the INFO code from
MULTICAL® 801 s/w rev. D1 or newer, and via M-bus, LON and
GSM/GPRS modules in info bits from MULTICAL®603 or 803.
|
Specifications
Controls and Indicators:
Status-, data- and alarm indicators, buzzer.
Key for alarm mute and acknowledge. Two digital control inputs.
Leak Monitor Volume:
Measuring period 210 sec.; truncated when threshold exceeded; alarm on successive errors.
Threshold adjustable 0.5-1-2-5%qp + 1-2-5-10%qact.
OptiTight®:
Execution: 0-4x/day, or by control input.
Start at 02:00 + 24 / 2*12 / 3*8 or 4*6 hours.
Threshold 20-40-60-80%qp, duration 5-10-20-40m.
Mains Connection:
230V 50Hz L/N/PE via key switch.
Power consumption max 20W.
Options
Liquid sensor attachment: (Opt. V)
Accepts two liquid sensors type LS-X,
for select protection of sensitive areas with optional cut-off.
SMS-alarm:
By attachment to AERS system KMP-F may text
mobile phone(s) on alarm.
Outdoor Temperature Sensor
Suppresses OptiTight® tightness test in cold weather, protecting unsecured calorifiers.
Drain valve:
Employed in critical applications for draining the heating system installation on leakage alarm.
Operating Pressure Monitor: (Opt. P)
Cuts off installation when operating pressure fails. Minimizes media loss and restart difficulty.
Options V and P are mutually exclusive.
|