Descriptions for tender
The following is suggested descriptions for use in tender material.
The majority hereof may be copied verbatim; wherever the text is
red, consultant must supply information or make a choice.
|
District heating
|
Leakage protection system that monitors flow difference at the specified
point in the installation, and issues an alarm and cuts off the protected
installation when the flow difference becomes unacceptable. Further, using
periodic asymmetric cut-off, the leakage protection system must detect
seepage and e.g. primary/secondary leakage in calorifiers, and likewise
issue an alarm and possibly cut-off the installation.
The leakage protection system must perform continuous or intermittent
self-testing of associated components.
The leakage protection system must feature an alarm relay output, and
volume impulse outputs for BMS (submetering).
The system must be based on flow measurement using static flow meters.
The combined head loss of all components of the leakage protection system
muts be no bigger than 1mWc (10 kPa) at Qmax=[fill in].
If a ventilation system draws outside air through a radiator fed by district
heating, add
EITHER:
The leakage protection system must be supplied with an outdoor temperature
sensor for blocking tightness test at low outdoor temperatures.
OR:
The leakage protection system must accept a signal from BMS for execution or
blocking of tightness test.
Energy Readout
Specify whether readout of energy transport from the leakage detection system
is required, and - if known - the type of data interface.
Propagation of alarms:
DanTaet Leakage Protection Systems are equipped with AERS.
In addition, you may specify:
__ technical alarm via e.g. Burglar Alarm or Fire Alarm
__ alarm to BMS
__ other: _________________________
|
|
Cooling water
|
Leakage protection system that monitors flow difference at the specified
point in the installation, and issues an alarm and cuts off the protected
installation when the flow difference becomes unacceptable.
The leakage protection system must perform continuous or intermittent
self-testing of associated components.
The leakage protection system must feature an alarm relay output, and
volume impulse outputs for BMS (submetering).
The system must be based on flow measurement using static flow meters.
Cooling installation Qmax=[fill in].
Caution! If the cooling medium is not pure water, all additives must
be listed and their concentration specified!
Propagation of alarms:
DanTaet Leakage Protection Systems are equipped with AERS.
In addition, you may specify:
__ technical alarm via e.g. Burglar Alarm or Fire Alarm
__ alarm to BMS
__ other: _________________________
|
|
Supply Water Commercial
general
|
Leakage protection system that monitors water usage at the specified point in the
installation, and issues an alarm and cuts off the relevant protected installation
when consumption becomes unacceptable.
The leakage protection system must permit monitoring with different sensitivities
depending on time-of-day or an external control signal from BMS, burglar alarm,
or other source.
The leakage protection system must allow override (force open) of the cut-off valve from
a fire alarm system or any fire hose cabinets fed from the protected installation.
The leakage control system must feature a run-in facility for use in the event of
permanent changes in consumption.
The leakage protection system must perform continuous or intermittent
self-testing of associated components, and must keep a log of alarms and other events.
The leakage protection system must feature an alarm relay output, and
volume impulse outputs for BMS (submetering).
For supply water, potable and pressurized water, the system must be based on flow
measurement using static flow meters.
Measuring point: specify
Qd' at measuring point: specify
Pipe dimension at measuring point: specify
No. of fire hoses fed by measuring point: specify
A branch that feeds fire hoses must have its cut-off valve specified SRNO.
If water at measuring point has been subjected to any treatment, the nature hereof must be specified.
Propagation of alarms:
DanTaet Leakage Protection Systems are equipped with AERS.
In addition, you may specify:
__ technical alarm via e.g. Burglar Alarm or Fire Alarm
__ alarm to BMS
__ other: _________________________
|
|
Supply Water Holiday and Rental Homes
|
Leakage protection system that monitors water usage in the water main DN
[fill in], and issues an alarm and cuts off the
installation when consumption becomes unacceptable.
The leakage protection system must permit monitoring with different sensitivities
depending on an external control signal from attached PIR sensors situated to cover the
taps of the property.
The leakage protection system must perform continuous or intermittent
self-testing of associated components.
The leakage protection system must feature an alarm relay output.
The system must be based on flow measurement using a static flow meter.
The installation's Qd=[specify].
Propagation of alarms:
DanTaet Leakage Protection Systems are equipped with AERS.
In addition, you may specify:
__ technical alarm via e.g. Burglar Alarm or Fire Alarm
__ other: _________________________
|
|
Water Aggregation Riser Shafts
|
Fail-safe, stand-along monitoring system for water aggregation in difficult-to-inspect and/or
infrequently visited locations, such as riser shafts and basement floor drains, which alarms
out visibly and audibly as well as by alarm relay in the event of water aggregation by the
sensor electrodes.
The system must be fail-safe so that it reports power supply, sensor and cable failures.
The sensor electrodes must be protected from galvanic corrosion by the use of an AC measuring current,
and from chemical corrosion by gold plating of the sensor electrodes.
The system must have an uncommitted alarm relay output for the attachment of an SMS alarm transmitter.
Propagation of alarms:
__ AERS
__ technical alarm via e.g. Burglar Alarm or Fire Alarm
__ alarm to BMS
__ other: _________________________
|
|
Alarm Propagation AERS
|
Alarms are conveyed as text message and/or e-mail to one or more duty officers.
Alarms may be distributed according to a preset duty schedule. A history (log) is maintained
of alarms and acknowledgements from each attached leakage protection system.
Consumption is recorded, permitting inspection of any condition that caused an alarm.
After such inspection, it is possible to remotely acknowledge an alarm.
More alarm sources can be accommodated.
Consumption on any attached meter is recorded and may be visualized.
Consumption reports may be generated automatically or on demand and are forwarded by e-mail.
|