Cooling Circuit Leakage Protection System KMP-K
|
Principle
Cooling Circuit Leakage Protection system KMP-K employs values of volume flow from two flow meters,
which are fetched regularly via a digital interface from a Kamstrup
MULTICAL®601, 602, 6M2, 603, 6M3, 801,
803 or 8M3 cooling meter to which the flow meters are attached.
Two monitoring functions are employed with the fetched flow data for protecting the installation
from leakage, as the KMP-K closes the cut-off valves when a leak is detected by any monitor.
Component errors reported in the heat meters's INFO code are propagated by the KMP-K as
System Fault alarm.
|
|
Logging
Alarm and Event log
KMP-K maintains a log over the most recent 250 events. Events include power down/up,
alarm and error reports, acknowledgements and autoreset, key input, control input
and sequencer action.
|
Jumper log
KMP-K maintains a log of the 15 most recent changes to the internal jumper setting.
These logs contribute to clarification and documentation of actual events.
|
AERS
On delivery, KMP-K is attached to the DanTaet Alarm and Energy Registration System AERS, which conveys
leakage alarms to the duty watch of the property and illustrates the event. AERS transmits
alarms in the form of text messages and/or e-mail, and alarms may be remotely acknowledged
from the recipient's smarthphone, tablet, laptop or PC.
Example: Situation view from AERS
|
|
|
System K6A (K8A) |
Capacity and Pressure Loss |
Dimensions |
Nom. Cap. qp (m³/h) |
ΣΔp@qp |
Equivalent Kv (m³/h) |
(mwc) |
(kPa) |
Flow Meter |
Valve |
Check Valve |
KMP-K6A1,5 |
1,5 |
3,5 |
35 |
2,6 |
G¾B x 110 mm (R½) |
½" x 77 mm |
½" x 48 mm |
KMP-K6A2,5 |
2,5 |
3,1 |
31 |
4,5 |
G1B x 190 mm (R¾) |
¾" x 77 mm |
¾" x 53 mm |
KMP-K6A3,5 |
3,5 |
2,3 |
23 |
7,4 |
G5/4B x 260 mm (R1) |
1" x 90 mm |
1" x 59 mm |
KMP-K6A6 |
6 |
4,6 |
46 |
8,8 |
G1½B x 260 mm (R5/4) |
1¼" x 110 mm |
1¼" x 66 mm |
KMP-K6A10 |
10 |
2,4 |
24 |
20 |
G2B x 300 mm (R1½) |
1½" x 120 mm |
1½" x 71 mm |
KMP-K6A10F |
10 |
2,4 |
24 |
20 |
DN40 x 300 mm |
1½" x 120 mm |
1½" x 71 mm |
KMP-K6A15 |
15 |
3,8 |
38 |
24 |
DN50 x 270 mm |
2" x 140 mm |
2" x 80 mm |
KMP-K6A25 |
25 |
2,4 |
24 |
51 |
DN65 x 300 mm |
DN65 x 46 mm |
DN65 x 54 mm |
KMP-K6A40 |
40 |
2,1 |
21 |
88 |
DN80 x 300 mm |
DN80 x 46 mm |
DN80 x 57 mm |
KMP-K6A60 |
60 |
1,3 |
13 |
169 |
DN100 x 360 mm |
DN100 x 52 mm |
DN100 x 64 mm |
KMP-K6A100 |
100 |
2,0 |
20 |
224 |
DN125 x 350 mm |
DN125 x 56 mm |
DN125 x 70 mm |
KMP-K6A150 |
150 |
0,83 |
8,3 |
519 |
DN150 x 500 mm |
DN150 x 56 mm |
DN150 x 76 mm |
KMP-K6A400 |
400 |
1,2 |
12 |
1162 |
DN200 x 500 mm |
DN200 x 60 mm |
DN200 x 95 mm |
KMP-K6A600 |
600 |
1,2 |
12 |
1723 |
DN250 x 600 mm |
DN250 x 68 mm |
DN250 x 108 mm |
KMP-K6A1000 |
1000 |
1,3 |
13 |
2779 |
DN300 x 500 mm |
DN300 x 78 mm |
DN300 x 143 mm |
|
KMP-K6M and KMP-K8M
Flow meters and valves are selected for each system individually according to
media type and operating conditions; hence there are no general system tables
for these families.
Variants
Variant -M2 is a complete new delivery.
Variants -M1 and -M0 are used with an existing Kamstrup cooling meter.
Note an existing cooling meter must be mains supplied for use with KMP-K.
The MULTICAL®803/8M3
calculator is used when the application requires more than two module slots.
|
Delivery KMP-K
Variant (suffix) |
-M2 |
-M1 |
-M0 |
KMP-K control unit |
1 |
1 |
1 |
Cut-off valves |
2 |
2 |
2 |
Check valve |
1 |
1 |
1 |
MULTICAL®calculator |
1 |
0 |
0 |
Flow meters |
2 |
1 |
0 |
Data module |
1 |
1 |
1 |
|